forked from evcc-io/evcc
-
Notifications
You must be signed in to change notification settings - Fork 0
Expand file tree
/
Copy patheltako-modbus.yaml
More file actions
138 lines (133 loc) · 3.08 KB
/
Copy patheltako-modbus.yaml
File metadata and controls
138 lines (133 loc) · 3.08 KB
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
template: eltako-modbus
products:
- brand: Eltako
description:
generic: DSZ15DZMOD
requirements:
description:
de: |
Getestet zusammen mit dem Modbus-Gateway von Eltako (ZGW16-IP)
Im Gateway müssen folgende Register aktiviert weerden: 30001, 30003, 30005, 30007, 30009, 30011, 30013, 30015, 30017, 30053, 30073, 30075
params:
- name: usage
choice: ["charge", "grid", "pv", "battery"]
- name: host
- name: port
default: 502
- name: meter_id
default: 1
description:
de: Modbus Slave-ID des spezifischen Zählers
en: Modbus slave id of the specific meter
render: |
type: custom
power: # current power
source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 52
type: input
decode: int32
timeout: 2s
energy: # meter in kwh
source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 72
type: input
decode: int32
timeout: 2s
scale: 0.01
returnenergy: # meter in kwh
source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 74
type: input
decode: int32
timeout: 2s
scale: 0.01
powers: # phase powers in W
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 12
type: input
decode: int32
timeout: 2s
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 14
type: input
decode: int32
timeout: 2s
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 16
type: input
decode: int32
timeout: 2s
currents: # phase currents in A
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 6
type: input
decode: int32
timeout: 2s
scale: 0.01
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 8
type: input
decode: int32
timeout: 2s
scale: 0.01
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 10
type: input
decode: int32
timeout: 2s
scale: 0.01
voltages: # phase voltages in V
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 0
type: input
decode: int32
timeout: 2s
scale: 0.01
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 2
type: input
decode: int32
timeout: 2s
scale: 0.01
- source: modbus
id: {{ .meter_id }}
uri: {{ joinHostPort .host .port }}
register:
address: 4
type: input
decode: int32
timeout: 2s
scale: 0.01