NP-0501DU Outlet Mapping - CRITICAL FINDINGS

Device: Synaccess netBooter NP-0501DU Firmware: Unknown Test Date: 2025-10-08 Tested By: Robert Sigler

🚨 INVERTED LOGIC DISCOVERED

CRITICAL: Outlets 1 and 5 have INVERTED status reporting. The device reports the OPPOSITE of the actual physical state.

Verified Mappings

Control Commands (rly=X)

rly Index Physical Outlet Status Position Logic Type
rly=0 Outlet 1 Position 4 (rightmost) INVERTED
rly=1 Outlet 2 Position 3 Unknown
rly=2 Outlet 3 Position 2 Unknown
rly=3 Outlet 4 Position 1 Unknown
rly=4 Outlet 5 Position 0 (leftmost) INVERTED

Status String Mapping

Status format: $A0,XXXXX,current,temp

The 5-character outlet string maps as follows:

Position: 0     1     2     3     4
Outlet:   5     4     3     2     1
Index:   [0]   [1]   [2]   [3]   [4]

Documentation confirmation: "The most right x for relay1" ✓ CORRECT

  • Rightmost bit (position 4) = Physical outlet 1
  • Leftmost bit (position 0) = Physical outlet 5

Inverted Logic Details

Physical Outlet 1

  • Control: rly=0
  • Status: Position 4 (rightmost)
  • Problem: When outlet 1 is physically ON:
    • Device reports: 0 (OFF)
    • Sending rly=0 changes status to 1 (ON)
    • But physical outlet turns OFF
  • Effect: Status bit is inverted from physical reality

Physical Outlet 5

  • Control: rly=4
  • Status: Position 0 (leftmost)
  • Problem: When outlet 5 is physically ON:
    • Device reports: 0 (OFF)
    • Sending rly=4 changes status to 1 (ON)
    • But physical outlet turns OFF
  • Effect: Status bit is inverted from physical reality

Test Results

Initial State

Physical Reality:  Outlet 1=ON, Outlet 5=ON, Others=OFF
Device Reports:    $A0,00000,0.15,XX (all OFF)
Current Draw:      0.15A (confirms power is being drawn)

Test: rly=0 (Physical Outlet 1)

Before:  00000  (Device says: all OFF)
Command: rly=0
After:   00001  (Device says: outlet 1 is now ON)
Reality: Physical outlet 1 turned OFF
Result:  ⚠️ INVERTED - Device reports opposite of reality

Test: rly=4 (Physical Outlet 5)

Before:  00000  (Device says: all OFF)
Command: rly=4
After:   10000  (Device says: outlet 5 is now ON)
Reality: Physical outlet 5 turned OFF
Result:  ⚠️ INVERTED - Device reports opposite of reality

Outstanding Questions

  1. Are outlets 2, 3, 4 also inverted? Need to test with loads connected
  2. Is this a firmware bug? Device might have a known issue
  3. Is this configurable? Web interface might have a setting for "Normally Open" vs "Normally Closed" relay logic
  4. Does this affect all NP-0501DU units? Or just this one?

Implications for Software Integration

Home Assistant Integration

  • MUST implement logic inversion for outlets 1 and 5
  • Cannot trust device status directly
  • Need configuration option to disable inversion (for other device models)

CLI Tool

  • Should detect inverted logic automatically
  • Warn user if detected
  • Provide --invert-outlets flag for affected outlets

API Client Library

class OutletConfig:
    outlet_number: int
    inverted_logic: bool = False  # Set True for outlets 1, 5 on NP-0501DU

def get_actual_state(reported_state: bool, inverted: bool) -> bool:
    """Get actual physical state accounting for inverted logic."""
    return not reported_state if inverted else reported_state

Recommended Next Steps

  1. COMPLETED: Test outlets 1 and 5
  2. TODO: Connect loads to outlets 2, 3, 4 and test for inverted logic
  3. TODO: Check device web interface for relay configuration settings
  4. TODO: Contact Synaccess support about firmware version and known issues
  5. TODO: Document whether this affects reboot commands (rb=X)
  6. TODO: Build software with configurable inversion per outlet

Safety Warnings

⚠️ DO NOT TRUST DEVICE STATUS FOR OUTLETS 1 AND 5

  • Device reports OFF when outlet is ON
  • Device reports ON when outlet is OFF
  • This could lead to:
    • Equipment damage (thinking power is off when it's on)
    • Safety hazards (attempting maintenance on "powered off" equipment)
    • Data loss (unexpected power cycles)

Hardware Workaround

If possible:

  • Use outlets 2, 3, 4 for critical loads
  • Keep outlets 1 and 5 for non-critical devices
  • Or implement software inversion (recommended)

Last Updated: 2025-10-08 Status: Partially tested - outlets 2, 3, 4 still need verification